Tinjauan:
JN15-12 grounding switch dirancang husus pikeun sistem kakuatan indoor 3-12KV kalawan tilu-fase AC 50Hz konfigurasi. Saklar na seamlessly cocog sareng sagala rupa setups switchgear tegangan tinggi. Éta minuhan standar GB1985-2004 sareng IEC129.
model: JN15-12
Struktur:
Bracket, grounding péso assembly, kontak statik, sensor, aci, siku, spring tekanan, leungeun baju conductive, sarta sambungan lemes.
data teknis:
| ITEM | UNIT | DATA |
| tegangan dipeunteun | KV | 12 |
| Dipeunteun waktos pondok tahan ayeuna | KA | 31.5 |
| Dipeunteun sirkuit pondok tahan waktos | S | 4 |
| Dipeunteun pondok circuit nyieun ayeuna | KA | 80 |
| Dipeunteun puncak tahan ayeuna | KA | 80 |
| Frékuénsi kakuatan 1min tahan tegangan | KV | 42 |
| Impuls kilat tahan tegangan | KV | 75 |
| Kahirupan mékanis | WAKTU | 2000 |
ukuran:
| Diménsi | E | F | G | H | D | C |
| JN15-12/31.5-165 | 165 | 75 | 160 | 565 | 426 | |
| JN15-12/31.5-180 | 180 | 75 | 160 | 595 | 456 | |
| JN15-12/31.5-200 | 200 | 75 | 160 | 635 | 496 | |
| JN15-12/31.5-210 | 210 | 75 | 160 | 655 | 516 | |
| JN15-12/31.5-220 | 220 | 75 | 160 | 675 | 536 | |
| JN15-12/31.5-230 | 230 | 75 | 160 | 695 | 556 | 96 |
| JN15-12/31.5-250 | 250 | 75 | 160 | 735 | 596 | 96 |
| JN15-12/31.5-275 | 275 | 75 | 185 | 810 | 646 | 96 |
UNIT: mm
Kaayaan lingkungan:
① Luhurna teu leuwih ti 1000m dpl.
② Suhu ambient henteu langkung luhur ti +40 ° C sareng henteu langkung handap -10 ° C.
③ Kalembaban relatif teu leuwih gede ti 95% dina rata-rata poean jeung teu leuwih gede ti 90% dina rata-rata bulanan.
④ Inténsitas seismik henteu ngaleuwihan 8 derajat.